Double-joint strain insulator fittings are the main equipment substations. It is great significance for reducing its maximum electric field strength to avoid corona noise and to improve substation electromagnetic environment. Firstly double-joint strain insulator string fittings simulation model is given by use of ansys 14.0, and the electric field is simulated and calculated according to the actual installation location of the related equipment. The construction for double-joint strain insulator string fittings is optimized to reduce the electric field value on basis of studying on the simula...